- Input type : Thermocouple: K, S, R, E, J, T, B, N, WRe5-WRe26 RTD: Pt100, Cu50, 0~20mV, 0~60mV, 0~100mV, 0~1V, 0.2~1V, 4-20mA, 0-20mA, 0-10V DC
- Retransmission accuracy : 0.3%FS 1 digit (including input and output error)
- Output Specification : can be freely defined in the range of 0~22mA with maximum output voltage 11V
- Temperature drift : 0.015%FS /C (including the temperature drift of input and output)
- Electromagnetic compatibility (EMC) : 4KV/5KHz according to IEC61000-4-4 (EFT); 4KV according to IEC61000-4-5.
- Isolation withstanding voltage : voltage between power, signal input and output terminals 2300VDC; between inputs or 2 outputs 200VDC
- Power supply : 100~240VAC, -15%, +10% / 50Hz; or 24VDC/AC.
- Power consumption : 3W
- Operating Ambient : Temperature -10~+60C; humidity 90%RH
- Note 1 : B thermocouple obtains the above measurement accuracy only at the range of 400~
- 1800 . It C s measurement from 60~400 . C is less accurate.
- Model no. AI-7021-D5